Today, let’s talk about how to interface with Omron PLC via Hostlink protocol.

Der Artikel, den wir zuvor besprochen haben:

Integration des EG Edge-Computing-Gateways mit General Electric PLC

Integration mit Xinjie PLC über Modbus RTU Protokoll

Schnittstelle zu Keyence-SPSen der Serie KV-8000 über das MC-3E-Protokoll

Schnittstelle zu Keyence-SPSen der Serie KV-7500 über das KV-TCP-Protokoll

How to interface with Panasonic PLCs via Mewtocol TCP Protocol

How to interface with Inovance PLC via Modbus RTU protocol

How to interface with AB PLC via PCCC protocol

How to interface with AB PLC via EtherNet/IP protocol

How to interface with Omron PLC via EtherNet/IP protocol

1. Hardware-Anschluss

Compatible PLC: CP Series

The Hostlink protocol uses serial communication. For this example, the PLC model CP1W-0026 uses RS485 communication. Simply connect the PLC’s 485 interface SDA- to the gateway’s B1 pin, and the PLC’s 485 interface SDB+ to the gateway’s A1 pin.

Interface with Omron PLC via Hostlink protocol01

2. PLC Serial Parameters

Note the unit number (station number 1) and baud rate (9600-8-1-E). These parameters will be required for subsequent gateway configuration.

Interface with Omron PLC via Hostlink protocol02

Note: DIP Switch Settings: 1 and 4 (OFF), 2, 3, 5, 6 (NO)

Interface with Omron PLC via Hostlink protocol03

3. Gateway-Konfiguration

3.1. PLC Connection Setup

Drag an Omron node from the left panel. Double-click to open the settings page and configure based on the PLC’s serial parameters as follows:
Protokoll: Select HostLink

Serial Port: Select RS485-1 (based on actual hardware connections)

Baud Rate: 9600

Data Bits: 8

Stop Bits: 1

Parity: EVEN

Station Number: 1

Interface with Omron PLC via Hostlink protocol04

3.2. Datenpunkt-Konfiguration

Enter the data points to be read in the Omron node’s parameter list. Once configured, the PLC data will be automatically retrieved at the set frequency. Data points are typically provided by PLC engineers. After obtaining the point list, enter data points in the format required by the gateway. For specific correspondence, refer to:(Sie können Google Chrome für die Übersetzung verwenden) https://iotrouter.yuque.com/zn3vdn/eg8000/skfapgdm7332it5q

In the parameter list, fill in Address/Name/Data Type/Data Length sequentially. Set a 2-second cycle for periodic reading, as shown in the figure:

Interface with Omron PLC via Hostlink protocol05

3.3. Prüfung

Click Deploy. Observe that a data point is printed every 2 seconds. Verify that the output value matches the actual value. Communication successful!

Interface with Omron PLC via Hostlink protocol06