Guide de l'utilisateur de la passerelle Edge Computing : Connexion aux automates Panasonic via le protocole Mewtocol TCP

This article shows how Panasonic PLCs can be integrated with the EG Edge Gateway via the Mewtocol TCP protocol for industrial communication. It belongs to the PLC Integration Hub.

1. Connexion du matériel

Compatible PLC: Panasonic FP0H / Panasonic XHC60ET

The MEWTOCOL TCP protocol uses Ethernet communication. Therefore, you only need to ensure that the gateway’s LAN port and the Panasonic PLC are configured within the same IP subnet.

Interface avec les automates Panasonic via le protocole TCP Mewtocol01

2. Paramètres de communication PLC

2.1 Ethernet Parameter Configuration

Interface with Panasonic PLCs via Mewtocol TCP Protocol02

2.2 User Connection Port Configuration

Interface with Panasonic PLCs via Mewtocol TCP Protocol03

3. Configuration de la passerelle

3.1 Paramètres de connexion de l'automate

Faire glisser un Panasonic node from the left panel, then double-click it to open the configuration page. Fill in the parameters according to the PLC communication settings as follows:

Protocole: MEWTOCOL TCP

Adresse: PLC IP address (example: 192.168.10.5)

Port: PLC connection port (example: 60001)

Connection Timeout: 2000

Communication Timeout: 2000

Station Number: EE

Interface with Panasonic PLCs via Mewtocol TCP Protocol04

3.2 Data Point Configuration

In the parameter list of the Panasonic node, enter the data points to be read. Once the data points are configured, the gateway will automatically read PLC data at the configured polling interval.

Data points are usually provided by the PLC engineer. After receiving the point list, fill in the data points according to the gateway’s required format. The detailed address mapping can be referenced here:(Vous pouvez utiliser Google Chrome pour la traduction)

https://iotrouter.yuque.com/zn3vdn/eg8000/frhrwhgsa8o2xpof

In this example, data is read from address DT0. Using the FPWIN GR7 software, you can see that the signed 32-bit integer stored in DT0 is 273. In the parameter list, fill in the address/name/data type/data length, and configure a 2-second polling interval, as shown in the figure.

Interface with Panasonic PLCs via Mewtocol TCP Protocol05

3.3 Tests

Cliquez sur Déployer. You will see one data record printed every 2 seconds. The read data result is:

DT0: 273

La communication a bien fonctionné !

Interface with Panasonic PLCs via Mewtocol TCP Protocol06

Guides connexes dans Intégration des automates industriels

← Retour au Hub d'intégration PLC

À propos de moi
db6893fd1d3e314ac461fa240068dc06?s=150&d=mp&r=g
Spécialiste en solutions IoT ~ Web ~  Plus d'articles

Agnes Wang est spécialiste des solutions IoT chez IOTRouter ; elle se consacre principalement aux passerelles IoT industrielles, à l'edge computing et aux solutions d'automatisation industrielle.

Elle est spécialisée dans les technologies de communication industrielle, notamment Modbus, la norme CEI 60870-5-104, MQTT, OPC UA, l'intégration d'automates programmables (PLC) et les applications de télésurveillance. Elle contribue à la rédaction d'articles techniques et de guides d'application consacrés aux solutions IoT industrielles, à la conversion de protocoles et à l'edge computing.