Edge Computing Gateway User Guide: Integration with Mitsubishi FX3U PLC via Programming Port Communication

This guide explains how to connect Mitsubishi FX3U PLCs to the EG8200Mini Edge Gateway via the programming port. It is part of the Protocol Hub, focusing on industrial communication and data exchange.

1. Ligação do hardware

Compatible PLC

Mitsubishi FX3U series PLCs and other Mitsubishi PLCs that support programming port communication.

Integration with Mitsubishi FX3U PLC

Ligação de hardware

Connect the PLC programming port to the RS232 interface of the EG8200Mini through a compatible conversion cable.

2. Parâmetros de comunicação do PLC

2.1 Serial Port Parameter Settings

The serial communication parameters should be provided by the PLC engineer.

3. Definições da porta de entrada

3.1 Definições de ligação do PLC

Arrastar um Mitsubishi node from the left panel and double-click it to open the configuration page. Configure the connection according to the PLC serial communication parameters as follows:

1  Protocol: FxSerial
2  Serial Port: RS232 (TX, RX, GND)
3  Baud Rate:9600
4  Data Bits:7
5  Stop Bits: 1
6  Parity: EVEN
7  Communication Timeout:2000 ms

Integration with Mitsubishi FX3U PLC2

3.2 Definições dos pontos de dados

Enter the data points to be read in the parameter list of the Mitsubishi node. After the data points are configured, the gateway will automatically read PLC data at the configured interval.

The PLC engineer usually provides the data points. After receiving the point table, enter the data points according to the format required by the gateway. For detailed address mapping information, refer to: (You can use Google Chrome for translation.)

https://iotrouter.yuque.com/zn3vdn/eg8000/gtyg0mdl9dipbu7u

In this example, data from the M0 address is read. In the parameter list, enter the Endereço, Nome, Tipo de dadose Data Length in sequence. The data is read in a 2-second cycle, as shown in the figure.

Integration with Mitsubishi FX3U PLC3

3.3 Ensaios

Integration with Mitsubishi FX3U PLC4

Clicar Implantar. A data record will be printed every 2 seconds. In this example, the result is displayed as:

M0: false

This indicates that communication has been established successfully.