Guida all'uso del gateway di Edge Computing: Come collegare i PLC della serie Delta DVP al gateway IoT tramite Modbus TCP

This guide offers a comprehensive solution for connecting Delta DVP, AS series, and other PLCs supporting the Protocollo Modbus TCP to IoT Edge Gateways. While these series share protocol compatibility, their addressing logic differs: DVP and AS models typically utilize fixed register maps, whereas the CODESYS-based AX-C12E used in this tutorial requires manual variable mapping through its Modbus TCP Slave component. We will demonstrate the communication configuration between the AX-C12E e il EG8200Mini gateway, specifically focusing on the Ethernet interface and data acquisition process.

Compatible PLCs include DVP series models e AS PLCs that support the Modbus TCP protocol.

1. Connessione hardware

Modbus TCP utilizes Ethernet communication. For this guide, the AX-C12E PLC is used. Simply connect the PLC’s Ethernet port to the LAN port of the gateway.

Connect Delta DVP Series PLCs to IoT Gateway via Modbus TCP

2. Parametri di comunicazione del PLC

The PLC engineer typically provides these parameters. In this example:

  • PLC IP Address: 192.168.1.121

  • Porto: 502

3. Configurazione del gateway

3.1. PLC Connection Setup

Trascina un Delta node from the left palette and double-click it to open the configuration page. Configure the PLC parameters as follows:

  • Protocollo: Modbus TCP

  • Porto: 502

  • Timeout della connessione: 2000 ms

  • Timeout di comunicazione: 2000 ms

  • Serie: AS

  • Unit ID (Station Number): 1

Connect Delta DVPAS Series PLCs to IoT Gateway via Modbus TCP2

3.2. Configurazione del punto dati

Enter the data points to be polled in the Parameter List. Once configured, the gateway will automatically read data from the PLC at the specified frequency.

Data points are usually provided by the PLC engineer in a point list. Map these points according to the gateway’s required format.

Connect Delta DVPAS Series PLCs to IoT Gateway via Modbus TCP3

3.3. Testing and Verification

Cliccare Distribuire. The gateway will log a data entry every 2 seconds. Observe the output to verify the result:

  • Received Value: D0: 88

Successful communication is confirmed.

Connect Delta DVPAS Series PLCs to IoT Gateway via Modbus TCP-test

Summary & Next Steps

With the communication channel established, your EG8200Mini is now ready to transform raw data from the Delta PLC into actionable insights. This Ethernet-based Modbus TCP connection ensures high-speed data transmission and provides the stability required for demanding industrial environments.

What’s Next?

  • Data Normalization: Use the gateway’s built-in edge computing capabilities to pre-process data before sending it to the cloud.

  • Alerting: Set up threshold-based alarms to monitor critical parameters in real-time.

  • Dashboarding: Visualize your D0 register data through the gateway’s local dashboard or an external SCADA system.

If you encounter any issues during the configuration process, please get in touch with our technical support team.

Guide correlate sull'integrazione dei PLC industriali

← Torna alla pagina "PLC Integration Hub"

About Me
db6893fd1d3e314ac461fa240068dc06?s=150&d=mp&r=g
IoT Solutions Specialist ~ Web ~  More Posts

Agnes Wang is an IoT Solutions Specialist at IOTRouter, focusing on industrial IoT gateways, edge computing, and industrial automation solutions.

She specializes in industrial communication technologies, including Modbus, IEC 60870-5-104, MQTT, OPC UA, PLC integration, and remote monitoring applications. She contributes to technical articles and application guides covering industrial IoT solutions, protocol conversion, and edge computing.