Today, let’s talk about how to interface the EG edge gateway with Inovance PLCs via the Modbus RTU Protocol.
Der Artikel, den wir zuvor besprochen haben:
Integration des EG Edge-Computing-Gateways mit General Electric PLC
Integration mit Xinjie PLC über Modbus RTU Protokoll
Schnittstelle zu Keyence-SPSen der Serie KV-8000 über das MC-3E-Protokoll
Schnittstelle zu Keyence-SPSen der Serie KV-7500 über das KV-TCP-Protokoll
How to interface with Panasonic PLCs via Mewtocol TCP Protocol
1. Hardware-Anschluss
Compatible PLC: Inovance H3U
The Modbus RTU protocol uses serial communication. This example PLC model employs RS232 communication.
2. PLC-Kommunikationsparameter
2.1. Serial Port Parameter Settings
Wird vom PLC-Ingenieur bereitgestellt.
The serial port parameters for this Inovance PLC are:
Baud Rate: 57600
Data Bits: 8
Stop Bits: 1
Parity Bit: NONE
3. Gateway-Konfiguration
3.1. PLC Connection Setup
Drag an Inovance node from the left pane. Double-click to open the settings page and configure as follows based on the PLC’s serial parameters:
Protokoll: Select Modbus RTU
Serial Port: RS232
Baud Rate: 57600
Data Bits: 8
Stop Bits: 1
Parity: None
Timeout: -1
Series: H3U
Station ID: 0x0B
Format: ABCD

3.2. Datenpunkt-Konfiguration
Enter the data points to be read into the parameter list of the Inovance node. Once configured, the node will automatically read data from the PLC at the specified frequency.
Data points are typically provided by PLC engineers. After obtaining the point list, fill in the data points according to the gateway’s required format. For specific mapping details, refer to:
This section contains a Yueque content card. Click the link to view:(Sie können Google Chrome für die Übersetzung verwenden) https://iotrouter.yuque.com/zn3vdn/eg8000/dqdvyosc5vubd2rv
This example reads data from addresses D6000 and D6002. In the parameter list, enter the address/name/data type in sequence. The data is read cyclically every 2 seconds, as shown in the figure:

3.3. Prüfung
Click Deploy and observe that data is printed every 2 seconds. The read data point results are: D6000:0 D6002:0. Communication successful!
