Today, let’s talk about how to interface the EG edge gateway with AB PLC via PCCC protocol.
The article we discussed before:
How to integration EG edge computing gateway with General Electric PLC
How to integration with Xinjie PLC via Modbus RTU protocol
How to interface with Keyence KV-8000 series PLCs via the MC-3E protocol
How to interface with Keyence KV-7500 series PLCs via the KV TCP protocol
How to interface with Panasonic PLCs via Mewtocol TCP Protocol
How to interface with Inovance PLC via Modbus RTU protocol
1. Подключение оборудования
Compatible PLC: AB SLC 5/05
The PCCC protocol utilizes Ethernet communication. Therefore, simply ensure the gateway’s LAN port and the AB PLC’s IP address are within the same subnet.

2. Параметры связи с ПЛК
2.1. Ethernet Parameter Settings
Provided by PLC Engineer
3. Gateway Settings
3.1. Настройки подключения ПЛК
Drag an AllenBradley node from the left panel, double-click to open the settings page, and configure as follows based on the PLC’s network port parameters:
Протокол: Select PCCC
Адрес: Введите адрес ПЛК (например, 192.168.0.59).
Порт: Enter the PLC connection port (e.g., 44818)
Таймаут соединения: 2000
Таймаут связи: 2000

3.2. Конфигурация точки данных
Enter the data points to be read into the parameter list of the Allen-Bradley node. Once configured, the PLC data will be automatically retrieved at the specified frequency.
Точки данных обычно предоставляются инженерами ПЛК. Получив список точек, заполните их в соответствии с требуемым форматом шлюза. Для получения подробной информации об отображении см:
В этом разделе содержится контент от Yueque. Нажмите на ссылку для просмотра:(You can use Google Chrome for translation) https://iotrouter.yuque.com/zn3vdn/eg8000/tcxbmwqbg7k7f5ah
This example reads data from address F8:1. In the parameter list, enter the address/name/data type/data length sequentially. The data is read cyclically every 2 seconds, as shown in the figure:

3.3. Testing
Connect to the debugging node, click Deploy, and observe that a data point is printed every 2 seconds. The read data point result is:
{F8:1:42669}. Communication successful!
