Анимация наведения

Edge Computing Gateway User Guide: Interface with AB PLC via PCCC protocol

Today, let’s talk about how to interface the EG edge gateway with AB PLC via PCCC protocol.

The article we discussed before:

How to integration EG edge computing gateway with General Electric PLC

How to integration with Xinjie PLC via Modbus RTU protocol

How to interface with Keyence KV-8000 series PLCs via the MC-3E protocol

How to interface with Keyence KV-7500 series PLCs via the KV TCP protocol

How to interface with Panasonic PLCs via Mewtocol TCP Protocol

How to interface with Inovance PLC via Modbus RTU protocol

1. Hardware Connection

Compatible PLC: AB SLC 5/05

The PCCC protocol utilizes Ethernet communication. Therefore, simply ensure the gateway’s LAN port and the AB PLC’s IP address are within the same subnet.

Interface with AB PLC via PCCC protocol01

2. PLC Communication Parameters

2.1. Ethernet Parameter Settings

Provided by PLC Engineer

3. Gateway Settings

3.1. PLC Connection Settings

Drag an AllenBradley node from the left panel, double-click to open the settings page, and configure as follows based on the PLC’s network port parameters:

Protocol: Select PCCC

Address: Enter the PLC address (e.g., 192.168.0.59)

Port: Enter the PLC connection port (e.g., 44818)

Connection Timeout: 2000

Communication Timeout: 2000

Interface with AB PLC via PCCC protocol02

3.2. Data Point Configuration

Enter the data points to be read into the parameter list of the Allen-Bradley node. Once configured, the PLC data will be automatically retrieved at the specified frequency.

Data points are typically provided by PLC engineers. Upon receiving the point list, fill in the data points according to the gateway’s required format. For specific mapping details, refer to:

This section contains content from Yueque. Click the link to view:(You can use Google Chrome for translation) https://iotrouter.yuque.com/zn3vdn/eg8000/tcxbmwqbg7k7f5ah

This example reads data from address F8:1. In the parameter list, enter the address/name/data type/data length sequentially. The data is read cyclically every 2 seconds, as shown in the figure:

Interface with AB PLC via PCCC protocol03

3.3. Testing

Connect to the debugging node, click Deploy, and observe that a data point is printed every 2 seconds. The read data point result is:

{F8:1:42669}. Communication successful!

Interface with AB PLC via PCCC protocol04

Свяжитесь с нами