Руководство пользователя Edge Computing Gateway: Интерфейс с ПЛК Xinjie по протоколу Modbus RTU

In this tutorial, we will focus on the EG series edge computing gateway with PLCs. We hope this proves helpful.

Статья, о которой мы говорили ранее:

How to integration EG edge computing gateway with the General Electric PLC

Today, let’s talk about how to integrate with Xinjie PLC.

Compatible PLC: Xinjie XD Series

1. Подключение оборудования

The Modbus RTU protocol utilizes serial communication. For this example, the PLC model XD3-16T employs RS485 communication. Simply connect the PLC’s 485 port A to the gateway’s A1, and the PLC’s 485 port B to the gateway’s B1.

Interface with Xinjie PLC via Modbus RTU protocol1

2. Параметры связи с ПЛК

2.1. Serial Port Parameter Settings

Interface with Xinjie PLC via Modbus RTU protocol2

3. Настройки шлюза

3.1. Настройки подключения ПЛК

Drag a XinJE node from the left panel and double-click to open its settings page. Configure the following based on your PLC’s serial port parameters:

Протокол: Select Modbus RTU

Последовательный порт: If connected to A1/B1, select RS485-1

Скорость передачи данных: 19200

Биты данных: 8

Стоп-биты: 1

Паритет: Even

Таймаут связи: 2000

Series: XD

ID станции: 1

Format: ABCD

Interface with Xinjie PLC via Modbus RTU protocol3

3.2. Конфигурация точки данных

Enter the data points to be read into the parameter list of the XinJE node. Once configured, the node will automatically read data from the PLC at the specified frequency.

Data points are typically provided by PLC engineers. After obtaining the point list, fill in the data points according to the gateway’s required format. For specific mapping details, refer to:

This section contains content from Yuque. Click the link to view: https://iotrouter.yuque.com/zn3vdn/eg8000/crnxbmg1g0p20geq

This example reads data from addresses M0 and D0. In the parameter list, enter the address/name/data type/data length in sequence. Data is read cyclically every 2 seconds, as shown in the figure:

Interface with Xinjie PLC via Modbus RTU protocol4

3.3. Тестирование

Click Deploy and observe that a data point is printed every 2 seconds. The read data point results are: M0:true, D0:3. Communication successful!

Interface with Xinjie PLC via Modbus RTU protocol5

Связанные руководства по интеграции промышленных ПЛК

← Вернуться на страницу «Центр интеграции ПЛК»

About Me
db6893fd1d3e314ac461fa240068dc06?s=150&d=mp&r=g
IoT Solutions Specialist ~ Web ~  More Posts

Agnes Wang is an IoT Solutions Specialist at IOTRouter, focusing on industrial IoT gateways, edge computing, and industrial automation solutions.

She specializes in industrial communication technologies, including Modbus, IEC 60870-5-104, MQTT, OPC UA, PLC integration, and remote monitoring applications. She contributes to technical articles and application guides covering industrial IoT solutions, protocol conversion, and edge computing.