Animação de pairar

Edge Computing Gateway User Guide: Interface with Omron PLC via Hostlink protocol

Today, let’s talk about how to interface with Omron PLC via Hostlink protocol.

O artigo que discutimos anteriormente:

Como integrar a gateway de computação periférica EG com a General Electric PLC

Como fazer a integração com o PLC Xinjie através do protocolo Modbus RTU

Como fazer a interface com os PLCs da série Keyence KV-8000 através do protocolo MC-3E

Como fazer a interface com os PLCs da série KV-7500 da Keyence através do protocolo KV TCP

Como fazer a interface com os PLCs da Panasonic através do protocolo TCP

How to interface with Inovance PLC via Modbus RTU protocol

How to interface with AB PLC via PCCC protocol

How to interface with AB PLC via EtherNet/IP protocol

How to interface with Omron PLC via EtherNet/IP protocol

1. Ligação do hardware

Compatible PLC: CP Series

The Hostlink protocol uses serial communication. For this example, the PLC model CP1W-0026 uses RS485 communication. Simply connect the PLC’s 485 interface SDA- to the gateway’s B1 pin, and the PLC’s 485 interface SDB+ to the gateway’s A1 pin.

Interface with Omron PLC via Hostlink protocol01

2. PLC Serial Parameters

Note the unit number (station number 1) and baud rate (9600-8-1-E). These parameters will be required for subsequent gateway configuration.

Interface with Omron PLC via Hostlink protocol02

Note: DIP Switch Settings: 1 and 4 (OFF), 2, 3, 5, 6 (NO)

Interface with Omron PLC via Hostlink protocol03

3. Configuração da porta de entrada

3.1. Configuração da ligação do PLC

Drag an Omron node from the left panel. Double-click to open the settings page and configure based on the PLC’s serial parameters as follows:
Protocolo: Select HostLink

Porta de série: Select RS485-1 (based on actual hardware connections)

Taxa de transmissão: 9600

Bits de dados: 8

Bits de paragem: 1

Paridade: EVEN

Station Number: 1

Interface with Omron PLC via Hostlink protocol04

3.2. Configuração do ponto de dados

Enter the data points to be read in the Omron node’s parameter list. Once configured, the PLC data will be automatically retrieved at the set frequency. Data points are typically provided by PLC engineers. After obtaining the point list, enter data points in the format required by the gateway. For specific correspondence, refer to:(Pode utilizar o Google Chrome para traduzir) https://iotrouter.yuque.com/zn3vdn/eg8000/skfapgdm7332it5q

In the parameter list, fill in Address/Name/Data Type/Data Length sequentially. Set a 2-second cycle for periodic reading, as shown in the figure:

Interface with Omron PLC via Hostlink protocol05

3.3. Ensaios

Click Deploy. Observe that a data point is printed every 2 seconds. Verify that the output value matches the actual value. Communication successful!

Interface with Omron PLC via Hostlink protocol06

Contactar-nos