Animación Hover

Guía del usuario de la pasarela Edge Computing: Interfaz con PLC Xinjie mediante protocolo Modbus RTU

En este tutorial, nos centraremos en la pasarela Edge Computing serie EG con PLCs. Esperamos que le resulte útil.

El artículo del que hablamos antes:

Cómo integrar la pasarela EG edge computing con General Electric PLC

Today, let’s talk about how to integration with Xinjie PLC.

Compatible PLC: Xinjie XD Series

1. Conexión de hardware

The Modbus RTU protocol utilizes serial communication. For this example, the PLC model XD3-16T employs RS485 communication. Simply connect the PLC’s 485 port A to the gateway’s A1, and the PLC’s 485 port B to the gateway’s B1.

Interface with Xinjie PLC via Modbus RTU protocol1

2. Parámetros de comunicación PLC

2.1. Serial Port Parameter Settings

Interface with Xinjie PLC via Modbus RTU protocol2

3. Configuración de la puerta de enlace

3.1. Configuración de la conexión del PLC

Drag a XinJE node from the left panel and double-click to open its settings page. Configure the following based on your PLC’s serial port parameters:

Protocolo: Select Modbus RTU

Serial Port: If connected to A1/B1, select RS485-1

Baud Rate: 19200

Data Bits: 8

Stop Bits: 1

Parity: Even

Tiempo de espera de comunicación: 2000

Series: XD

Identificación de la estación: 1

Format: ABCD

Interface with Xinjie PLC via Modbus RTU protocol3

3.2. Configuración de los puntos de datos

Enter the data points to be read into the parameter list of the XinJE node. Once configured, the node will automatically read data from the PLC at the specified frequency.

Data points are typically provided by PLC engineers. After obtaining the point list, fill in the data points according to the gateway’s required format. For specific mapping details, refer to:

This section contains content from Yuque. Click the link to view: https://iotrouter.yuque.com/zn3vdn/eg8000/crnxbmg1g0p20geq

This example reads data from addresses M0 and D0. In the parameter list, enter the address/name/data type/data length in sequence. Data is read cyclically every 2 seconds, as shown in the figure:

Interface with Xinjie PLC via Modbus RTU protocol4

3.3. Pruebas

Click Deploy and observe that a data point is printed every 2 seconds. The read data point results are: M0:true, D0:3. Communication successful!

Interface with Xinjie PLC via Modbus RTU protocol5

Póngase en contacto con nosotros