Edge Computing Gateway User Guide: Interface with Omron PLC via EtherNet/IP protocol

Today, let’s talk about how to interface with Omron PLC via EtherNet/IP protocol.

O artigo que discutimos anteriormente:

Como integrar a gateway de computação periférica EG com a General Electric PLC

Como fazer a integração com o PLC Xinjie através do protocolo Modbus RTU

Como fazer a interface com os PLCs da série Keyence KV-8000 através do protocolo MC-3E

Como fazer a interface com os PLCs da série KV-7500 da Keyence através do protocolo KV TCP

Como fazer a interface com os PLCs da Panasonic através do protocolo TCP

How to interface with Inovance PLC via Modbus RTU protocol

How to interface with AB PLC via PCCC protocol

How to interface with AB PLC via EtherNet/IP protocol

1. Ligação do hardware

Compatible PLC: NX7

The Fins protocol utilizes Ethernet communication. Therefore, it is only necessary to ensure that the LAN port IP address of the gateway and the IP address of the Omron PLC are within the same subnet (Note: In special cases, they may not be on the same subnet, requiring route configuration; consult technical support for details). The IP address allocation for this example is as follows:

EG8200Mini

Omron PLC
IP Address 192.168.250.4 192.168.250.10

2. Parâmetros de comunicação do PLC

2.1. Ethernet Parameter Settings

Interface with Omron PLC via EtherNetIP protocol1

2.2. Variable Address

Interface with Omron PLC via EtherNetIP protocol2

3. Definições da porta de entrada

3.1. Definições de ligação do PLC

Drag an Omron node from the left panel and double-click to open the settings page. Configure the following based on the PLC’s serial port parameters:

Protocolo: Select Fins

Endereço: Enter the PLC address (e.g., 192.168.250.10)

Porto: Enter the PLC connection port (e.g., 44818)

Tempo limite de ligação: 2000

Tempo limite de comunicação: 2000

Mode: TCP

SIot: 0

Interface with Omron PLC via EtherNetIP protocol3

3.2. Configuração do ponto de dados

Enter the data points to be read into the parameter list of the Omron node. Once configured, the PLC data will be automatically retrieved at the specified frequency.

Data points are typically provided by PLC engineers. Upon receiving the point list, fill in the data points according to the gateway’s required format. For specific correspondence, refer to:

This is a Yueque content card. Click the link to view:(Pode utilizar o Google Chrome para traduzir)

https://iotrouter.yuque.com/zn3vdn/eg8000/skfapgdm7332it5q

This example reads data from addresses A_MES_Heart and A_MES_Bind_C. In the parameter list, enter the address/name/data type/data length in sequence. Data is read cyclically every 2 seconds, as shown in the figure:

Interface with Omron PLC via EtherNetIP protocol4

3.3. Ensaios

Click Deploy and observe that a data point is printed every 2 seconds. The read data point results are: D100: false, D102: 99. Communication successful!

Interface with Omron PLC via EtherNetIP protocol5