Edge Computing Gateway User Guide: Interface with Panasonic PLCs via Mewtocol TCP Protocol

Today, let’s talk about how to interface the EG edge gateway with Panasonic PLCs via the Mewtocol TCP Protocol. 

O artigo que discutimos anteriormente:

Como integrar a gateway de computação periférica EG com a General Electric PLC

Como fazer a integração com o PLC Xinjie através do protocolo Modbus RTU

Como fazer a interface com os PLCs da série Keyence KV-8000 através do protocolo MC-3E

Como fazer a interface com os PLCs da série KV-7500 da Keyence através do protocolo KV TCP

Compatible PLCs: Panasonic FP0H / Panasonic XHC60ET

1. Ligação do hardware

Mewtocol TCP protocol communicates via Ethernet. Therefore, simply ensure the gateway’s LAN port and the Panasonic PLC’s IP address are within the same subnet.

Interface with Panasonic PLCs via Mewtocol TCP Protocol01

2. Parâmetros de comunicação do PLC

2.1. Ethernet Parameter Settings

Interface with Panasonic PLCs via Mewtocol TCP Protocol02

2.2. User Connection Port Settings

Interface with Panasonic PLCs via Mewtocol TCP Protocol03

3. Definições da porta de entrada

3.1. Definições de ligação do PLC

Drag a Panasonic node from the left panel and double-click to open its settings page. Configure the following based on the PLC’s serial port parameters:

Protocolo: Select Mewtocol TCP

Endereço: Enter the PLC address (e.g., 192.168.10.5)

Porto: Enter the PLC connection port (e.g., 60001)

Tempo limite de ligação: 2000

Tempo limite de comunicação: 2000

ID da estação: EE

Interface with Panasonic PLCs via Mewtocol TCP Protocol04

3.2. Configuração do ponto de dados

Enter the data points to be read into the parameter list of the Panasonic node. Once configured, the PLC data will be automatically retrieved at the specified frequency.

Data points are typically provided by PLC engineers. Upon receiving the point list, fill in the data points according to the gateway’s required format. For specific correspondence, refer to:

This is a Yuque content card. Click the link to view:(Pode utilizar o Google Chrome para traduzir) https://iotrouter.yuque.com/zn3vdn/eg8000/frhrwhgsa8o2xpof

This example reads data from address DT0. Using FPWIN GR7 software, you can see that DT0 stores a signed 32-bit integer: 273. In the parameter list, fill in the address/name/data type/data length sequentially. Set a 2-second cycle for periodic reading, as shown in the figure:

Interface with Panasonic PLCs via Mewtocol TCP Protocol05

3.3. Ensaios

Click Deploy and observe that a data point is printed every 2 seconds. The read data point result is: DT0:273. Communication successful!

Interface with Panasonic PLCs via Mewtocol TCP Protocol06