ZHC1921 Ethernet Modbus RTU - IOTROUTER
Search
Chinese New Year Holiday Notice (Feb 5–23) – IOTRouter wishes you a Happy New Year!

ZHC1921 Ethernet Modbus RTU

  • 4 relay outputs
  • 6 DI (dry/wet)
  • 2 PI (pulse) counting
  • 4 analog (current) inputs
  • TCP client/server, MQTT client, Modbus RTU/TCP
  • RS485 host/slave mode, supports cascading multiple devices

Features

  • Cloud forwarding and networking
  • Local and inter-device logic
  • Network registration and heartbeat packages
  • Hardware watchdog
  • Remote configuration and upgrade via host or web
  • Data trigger and regular reporting

Categories: ,

Description

ZHC1921 Ethernet Modbus RTU is a network IO product that supports 6 channels of dry (wet) node detection, 4 channels of relay (COM, NO) output, 4 channels of analog (current 4~20mA) detection, and one serial port transparent transmission. It is compatible with Modbus RTU/TCP protocol. With “remote control” as the core function, it is highly easy to use, and users can easily and quickly integrate into their own systems to realize Remote, LAN, and local control of Ethernet and RS485.

ZHC1921 ZHC1921 ZHC1921 ZHC1921 ZHC1921 ZHC1921 ZHC1921 ZHC1921ZHC1921ZHC1921ZHC1921ZHC1921ZHC1921ZHC1921 14ZHC1921ZHC1921ZHC1921ZHC1921ZHC1921ZHC1921ZHC1921ZHC1921ZHC1921

Datasheet

Network parametersSerial port
Network TypeEthernetnumber of portsRS485*1
Number of network ports (10/100M)LAN *1standardRS485: A, B
Network port typeEthernet signal RJ45baud rate600~921600bps
Electromagnetic isolation protection1.5KV Electromagnetic Isolationdata bits8, 9
Crossover direct connection automatic switching--stop bit0.5 , 1 , 1.5 , 2
External network transformerunnecessaryCheck DigitNONE EVEN ODD
DOAI
Number of interfaces4 switching outputsNumber of interfaces4 analog inputs
StandardNO*4, COM*4standardAI*4, GND*2
Mechanical durability10^7scope of test4~20mA
Electrical durability10^5
Capacity5API
250VAC 30VDCNumber of interfaces2 pulse count
StandardPI*2, COM*1
DIExamination Range10000Hz
Number of interfaces6 switch inputs
StandardDI*6, COM*1EMC
Detection range (wet node)5~50V->HighESDIEC61000-4-2, Level 4
0~2V->LowSurgeIEC61000-4-2, Level 3
Group PulseIEC61000-4-2, Level 3
Power supply
Voltage12~36V
Current60mA(aver) @12V
30mA(aver) @36V

Download

Contact Us

Contact Us