In deze tutorial richten we ons op EG series edge computing gateway met PLC's. We hopen dat dit nuttig is.
Het artikel dat we eerder bespraken:
Hoe EG edge computing gateway integreren met General Electric PLC
Today, let’s talk about how to integration with Xinjie PLC.
Compatible PLC: Xinjie XD Series
1. Hardwareverbinding
The Modbus RTU protocol utilizes serial communication. For this example, the PLC model XD3-16T employs RS485 communication. Simply connect the PLC’s 485 port A to the gateway’s A1, and the PLC’s 485 port B to the gateway’s B1.

2. PLC-communicatieparameters
2.1. Serial Port Parameter Settings

3. Gateway-instellingen
3.1. PLC-verbindingsinstellingen
Drag a XinJE node from the left panel and double-click to open its settings page. Configure the following based on your PLC’s serial port parameters:
Protocol: Select Modbus RTU
Serial Port: If connected to A1/B1, select RS485-1
Baud Rate: 19200
Data Bits: 8
Stop Bits: 1
Parity: Even
Time-out communicatie: 2000
Series: XD
Station ID: 1
Format: ABCD

3.2. Configuratie gegevenspunt
Enter the data points to be read into the parameter list of the XinJE node. Once configured, the node will automatically read data from the PLC at the specified frequency.
Data points are typically provided by PLC engineers. After obtaining the point list, fill in the data points according to the gateway’s required format. For specific mapping details, refer to:
This section contains content from Yuque. Click the link to view: https://iotrouter.yuque.com/zn3vdn/eg8000/crnxbmg1g0p20geq
This example reads data from addresses M0 and D0. In the parameter list, enter the address/name/data type/data length in sequence. Data is read cyclically every 2 seconds, as shown in the figure:

3.3. Testen
Click Deploy and observe that a data point is printed every 2 seconds. The read data point results are: M0:true, D0:3. Communication successful!